1. Components are allowed to work under the following conditions:
A. The relative humidity of the air is not more than 95%, and there is no explosive and corrosive gas (except for explosion-proof heater).
B. The working voltage shall not be greater than 1.1 times of the rated value, and the enclosure shall be effectively grounded.
C. Insulation resistance ≥ 1M Ω Dielectric strength: 2KV/1min.
2. The electric heating pipe shall be positioned and fixed properly. The effective heating area must be completely immersed in liquid or metal solid. It is strictly prohibited to burn empty. If scale or carbon deposit is found on the surface of the pipe body, it shall be cleaned and reused in time to avoid affecting heat dissipation and shortening the service life.
3. When heating the fusible metal or solid nitrate, alkali, asphalt, paraffin, etc., the operating voltage should be reduced first, and the rated voltage can only be increased after the medium is melted.
4. When heating the air, the elements shall be arranged in a cross and uniform manner to make the elements have good heat dissipation conditions, so that the air flowing through can be fully heated.
5. Safety measures shall be taken when heating nitrate to prevent explosion accidents.
6. The wiring part shall be placed outside the insulation layer to avoid contact with corrosive and explosive media and water; The lead wire shall be able to bear the temperature and heating load of the wiring part for a long time, and excessive force shall be avoided when fastening the wiring screws.
7. The element shall be stored in a dry place. If the insulation resistance is lower than 1M Ω due to long-term storage, it can be dried in an oven at about 200 ℃, or the voltage can be reduced and heated until the insulation resistance is restored.
8. Magnesia powder at the outlet end of the electric heating pipe shall be protected from pollutants and moisture in the place of use to prevent leakage accidents.
9. Non staff, please do not operate.